Four RECOMMENDATION have to take into account in the time of Busbar Trunking (BBT) Design and Installation!!
Recommendation 1
For industrial installations, remember to take into account the upgrading of the machine equipment base. As for a switchboard, a 20 % margin is recommended.
In ≤ IB x 1.2
For Example, at a brunch of a BBT, the load is 500 A. In that case, the BBT rating will be = 500 X 20% = 600 A.
Recommendation 2
A waterproof curb has to be recommended to install at each floor opening where busway passes.
Waterproof Curb/remondas.blogspot.com |
Recommendation 3
For an indoor application, fire barrier is recommended between the floors.
Fire Barrier/remondas.blogspot.comRecommendation 4
For outdoor application, an integral weather seal like canopy is recommended.
|